Introduction

The NDR Series of DIN rail power supplies is designed specifically for use in industrial applications. The 40 to 63 mm slim form-factor enables the power supplies to be easily installed in small and confined spaces such as cabinets. The broad operating temperature range of -20 to 70°C means they are capable of operating in harsh environments. The devices have a metal housing, an AC input range from 90 VAC to 264 VAC, and conform to the EN 61000-3-2 standard. In addition, these power supplies feature constant current mode to provide overload protection.

Models in this series (3)

NDR-120-24NDR-120-48NDR-240-48
Input Voltage90 to 264 VAC 47 to 63 Hz 127 to 370 VDC90 to 264 VAC 47 to 63 Hz 127 to 370 VDC90 to 264 VAC 47 to 63 Hz 127 to 370 VDC
Wattage120 W120 W240 W
Output Voltage24 V48 V48 V
Rated Current5 A2.5 A5 A
Operating Temp.-20 to 70°C-20 to 70°C-20 to 70°C
Add to Quote View Bag Buy from distributors (for USA only)Add to Quote View Bag Buy from distributors (for USA only)Add to Quote View Bag Buy from distributors (for USA only)

Specifications

Shown for NDR-120-24. Per-model differences are listed in the selection grid above.

Output Power Parameters

Wattage
120 W
Voltage
24 VDC
Current Rating
0 to 5 A
Ripple and Noise
120 mVp-p
Voltage Adjustment Range
24 to 28 VDC
Setup/Rise Time at Full Load
2500 ms, 60 ms at 115 VAC 1200 ms, 60 ms at 230 VAC
Typical Hold Up Time at Full Load
10 ms at 115 VAC 16 ms at 230 VAC

Input Power Parameters

Typical Efficiency
88%
Typical Current
1.3 A @ 230 VAC, 2.25 A @ 115 VAC
Voltage Range
90 to 264 VAC (47 to 63 Hz) 127 to 370 VDC
Inrush Current (cold start)
35 A @ 230 VAC, 20 A @ 115 VAC

Overload Protection

Rated Output Power
105 to 160%
Protection Type
Constant current limiting, recovers automatically after fault condition is removed

Overvoltage Protection

Overvoltage Range
29 to 33 V
Protection Type
Shut down operating voltage, repower on to recover

Physical Characteristics

Housing
Metal
Dimensions
123.75 x 125.20 x 40 mm (4.87 x 4.93 x 1.57 in)
Weight
500 g (1.10 lb)

Environmental Limits

Operating Temperature
-20 to 70°C (-4 to 158°F)
Storage Temperature
-40 to 85°C (-40 to 185°F)
Ambient Relative Humidity
20 to 95% (non-condensing)
Max. Operating Temperature at Full Load
45°C (113°F)

Standards and Certifications

Safety
UL 508 EN 62368-1 IEC 62368-1
EMC
EN 55032/35 EN 61000-3-2 Class A EN 61000-3-3 EN IEC 61204-3 EN IEC 61000-6-2
EMS
IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m IEC 61000-4-4 EFT: Power: 2 kV IEC 61000-4-5 Surge: Power: 4 kV IEC 61000-4-6 CS: 0.15 kHz to 80 MHz: 10 Vrms IEC 61000-4-8: 30 A/m IEC 61000-4-11

MTBF

Standards
MIL-HDBK-217F
Time
453,334 hrs

Warranty

Warranty Period
3 years
Details