Specifications
Input/Output Interface
- Thermocouple Channels
- 8
- Isolation
- 3k VDC or 2k Vrms
Thermocouples
- Connector
- Spring-type Euroblock terminal
- Sensor Type
- J, K, T, E, R, S, B, N
- Millivolt Type
- ±19.532 mV ±39.062 mV ±78.126 mV
- Converter Resolution
- 16 bits
- Millivolt Accuracy
- ±0.1% FSR @ 25°C ±0.3% FSR @ -40 and 75°C
- Sampling Rate
- All channels: 12 samples/sec Per channel: 1.5 samples/sec
- Input Impedance
- 1 mega-ohms (min.)
Power Consumption
- System Power
- 148.1 mA @ 3.3 VDC
Physical Characteristics
- Housing
- Plastic
- Dimensions
- 19.5 x 99 x 60.5 mm (0.77 x 3.90 x 2.38 in)
- Weight
- 78.4 g (0.173 lb)
- Installation
- DIN-rail mounting
- Strip Length
- I/O cable, 9 to 10 mm
- Wiring
- 18 to 24 AWG
Environmental Limits
- Operating Temperature
- -40 to 75°C (-40 to 167°F)
- Storage Temperature (package included)
- -40 to 85°C (-40 to 185°F)
- Ambient Relative Humidity
- 5 to 95% (non-condensing)
- Altitude
- Up to 4000 meters Please contact Moxa if you require products guaranteed to function properly at higher altitudes.
Standards and Certifications
- EMC
- EN 55032/35
- EMI
- CISPR 32, FCC Part 15B Class A
- EMS
- IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV IEC 61000-4-3 RS: 80 MHz to 1 GHz: 3 V/m IEC 61000-4-4 EFT: Power: 1 kV; Signal: 0.5 kV IEC 61000-4-5 Surge: Power: 2 kV; Signal: 1 kV IEC 61000-4-6 CS: 3 V IEC 61000-4-8 PFMF
- Shock
- IEC 60068-2-27
- Vibration
- IEC 60068-2-6
- Safety
- UL 61010-2-201
- Hazardous Locations
- ATEX Class I Division 2
Declaration
- Green Product
- RoHS, CRoHS, WEEE
MTBF
- Time
- 1,649,892 hrs
- Standards
- Telcordia Standard SR-332
Warranty
- Warranty Period
- 5 years
- Details