Specifications
Input/Output Interface
- Analog Output Channels
- 8
- Isolation
- 65M-3600-CT-T/65M-3610-CT-T/65M-4820-CT-T/65M-5801-CT-T: - Between signal and system: 3k VDC - Between groups: 1k VDC per min All other models: - Between signal and system: 3k VDC
Digital Inputs
- I/O Type
- Sink (Internal/external field circuit supply for dry contact)
- I/O Mode
- DI or event counter (channels 1 to 8, group configurable by software)
- Internal Field Circuit Supply Voltage
- 24 VDC 22.8 to 25.2 VDC
- Internal Field Circuit Supply Current
- 125 mA (max.) (Only for dry contact)
- Input Voltage
- On: 11 to 30 VDC Off: 0 to 5 VDC
- Input Current (voltage on)
- 2.35 mA ± 20% per channel
- Counter Frequency
- Square wave: 0 to 10 kHz
- Digital Filtering Time Interval
- Software configurable
- Diagnostics
- Input Wire-break Detection (current: 50 µA max., delay: 20 ms) Internal Field Circuit Supply Detection (17.5 VDC, 16 to 19 VDC)
Digital Outputs
- I/O Type
- Source
- I/O Mode
- DO or pulse output (channel 1 to 8, group configurable by software)
- Common Power Input Voltage
- 24 VDC 19.2 to 28.8 VDC
- Common Power Input Current
- 6.4 A (max.)
- Load Current
- 200 mA/channel (typ.) 500 mA/channel (max.)
- Pulse Duration
- 500 μs
- Protection
- Output Short-circuit Protection Common Power Input Over-voltage Protection Inductive Load Shutdown Voltage Protection
- Diagnostics
- Wire Break Detection (on state, output current < 3 mA) Wire Break Detection (off state, output load impedance > 58 kilo-ohms) Output Short-Circuit Detection (output current > 0.87 A, range: 0.64 to 1.2 A) External Power Detection (17.5 VDC, 16 to 19 VDC) Failsafe Configuration (hold last/failsafe state)
Analog Inputs
- I/O Mode
- 65M-3600-CT-T: Current 65M-3610-CT-T: Voltage 65M-3800H-CT-T: HART
- I/O Type
- Differential
- Input Range
- 65M-3600-CT-T: 0 to 20 mA 4 to 20 mA 65M-3610-CT-T: 0 to 10 V 1 to 5 V 65M-3800H-CT-T: 4 to 20 mA
- Overload Permitted on Inputs
- 65M-3600-CT-T: ±30 mA 65M-3610-CT-T: ±12 V 65M-3800H-CT-T: 30 mA
- Converter Resolution
- 16 bits
- Measurement Resolution
- 65M-3600-CT-T: 2 μA (0 to 20 mA) 1.6 μA (4 to 20 mA) 65M-3610-CT-T: 1 mV (0 to 10 V) 0.4 mV (1 to 5 V) 65M-3800H-CT-T: 1.6 μA (4 to 20 mA)
- Accuracy
- ±0.1% FSR @ 25°C ±0.3% FSR @ -40 to 75°C
- Conversion Time
- 100 ms
- Rejection Ratio
- Normal mode: > 60 dB @ 60 Hz (min.), conversion time: 100 ms Common mode: > 90 dB @ 60 Hz (min.), conversion time: 100 ms
- Input Impedance
- 65M-3800H-CT-T: 250 ohms 65M-3600-CT-T: 250 ohms 65M-3610-CT-T: 1 mega-ohms
- Diagnostics
- 65M-3800H-CT-T: Input Wire-break Input Short-circuit Input Underflow/Overflow Detection 65M-3600-CT-T: Internal Loop Power Detection (17.5 VDA, 16 to 19 VDC) Input Short-circuit Detection 65M-3600-CT-T (in 4 to 20 mA mode): Input Wire-break Detection (delay: 0.8 s) 65M-3610-CT-T: Input Wire-break Detection (delay:1.6 s max)
Analog Outputs
- I/O Mode
- Voltage/Current
- Output Range
- 0 to 10 V 1 to 5 V 0 to 20 mA 4 to 20 mA
- Converter Resolution
- 16-bit
- Output Resolution
- 1 mV (0 to 10 V) 0.4 mV (1 to 5 V) 2 μA (0 to 20 mA) 1.6 μA (4 to 20 mA)
- Accuracy
- ±0.1% FSR @ 25°C ±0.3% FSR @ -40 to 75°C
- Output Refresh Time
- 16 ms
- Output Impedance
- Voltage mode: 1 kilo-ohms (min.) Current mode: 750 ohms (max.)
- Diagnostics
- Output Short-circuit Detection (voltage) Failsafe Configuration (hold last/failsafe state) Output Wire-break Detection (current)
Serial Interface
- Serial Standards
- RS-232, RS-422, RS-485-2w
- Baudrate
- 300, 600, 1200, 1800, 2400, 4800, 9600, 19200, 38400, 57600, and 115200 bps
- Data Bits
- 7, 8
- Stop Bits
- 1, 2
- Parity
- None Even Odd
- Flow Control
- RTS/CTS, XON/XOFF
- Serial Signals
- RS-232: TxD, RxD, RTS, CTS, GND RS-422: Tx+, Tx-, Rx+, Rx-, GND RS-485-2w: Data+, Data-, GND
Terminal Blocks
- Connector
- Screw-fastened terminal block
- Dimensions
- 42.3 x 102.38 x 80.8 mm (1.67 x 4.03 x 3.18 in)
- Weight
- 164 g (0.36 lb)
Power Consumption
- System Power
- 65M-1900-CT-T/65M-2901-CT-T: 0.068 A @ 12 VDC 65M-3610-CT-T/65M-4820-CT-T: 0.069 A @ 12 VDC 65M-3600-CT-T: 0.073 A @ 12 VDC 65M-3800H-CT-T: 0.072 A @ 12 VDC 65M-5801-CT-T: 0.143 @ 12 VDC
- Field Power
- 65M-1900-CT-T: 0.019 A @ 24 VDC (without internal field circuit supply) 0.115 A @ 24 VDC (32-channel dry contact with internal field circuit supply) 65M-2901-CT-T: 0.005 A @ 24 VDC 65M-3600-CT-T: 0.053 A @ 24 VDC (without internal loop power) 0.466 A @ 24 VDC (16-channel 20 mA input with internal loop power) 65M-3610-CT-T: 0.038 A @ 24 VDC 65M-3800H-CT-T: 0.05 A (max.) @ 24 VDC (without internal loop power) 0.25 A (max.) @ 24 VDC (8-channel 4 to 20 mA input with internal loop power all in 20 mA) 0.66 A (max.) @ 24 VDC (500 mA input with internal loop power) 65M-4820-CT-T: 0.022 A @ 24 VDC (without external load) 0.266 A @ 24 VDC (4-channel 20 mA output) 65M-5801-CT-T: 0.11 A @ 24 VDC
Physical Characteristics
- Housing
- Plastic
- Dimensions
- 42 x 116 x 130 mm (1.65 x 4,57 x 5.12 in)
- Weight
- 257 g (0.57 lb)
Environmental Limits
- Operating Temperature
- -40 to 75°C (-40 to 167°F) Note: Proper airflow is required in an environment with temperature > 65°C.
- Storage Temperature (package included)
- -40 to 85°C (-40 to 185°F)
- Ambient Relative Humidity
- 5 to 95% (non-condensing)
- Altitude
- Up to 2000 meters Please contact Moxa if you require products guaranteed to function properly at higher altitudes.
Standards and Certifications
- EMC
- EN 55032/35 EN 61000-6-2/-6-4
- EMI
- CISPR 32, FCC Part 15B Class A
- EMS
- IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m IEC 61000-4-4 EFT: Power: (DC) 1 kV; Signal: 1 kV IEC 61000-4-5 Surge: Power: (DC) 0.5 kV L-N, 1 kV L/N-PE; Signal: 1 kV; IO: 0.5 kV IEC 61000-4-6 CS: Power: (DC) 10 V; Signal: 10 Vrms IEC 61000-4-8 PFMF: 30 A/m
- Safety
- UL 61010-1 UL 61010-2-201
- Shock
- IEC 60068-2-27 Half sine wave; acceleration: 15 g; time: 11 ms
- Vibration
- IEC 60068-2-6 DIN-rail mounted: 7 mm peak-peak (p-p) (2 to 8.42 Hz), 1 g (8.42 to 150 Hz) Rack mounted (with optional kit): 7 mm peak-peak (p-p) (2 to 8.42 Hz), 0.5 g (8.42 to 150 Hz)
MTBF
- Time
- 1,874,152 hrs
- Standards
- Telcordia Standard SR-332
Warranty
- Warranty Period
- 5 years
- Details
- See www.moxa.com/warranty