Specifications
System Power Parameters
- Power Connector
- Screw-fastened Euroblock terminal
- No. of Power Inputs
- 1
- Input Voltage
- Nominal value: 24 VDC Acceptable range: 21.6 to 26.4 VDC
- Input Current
- 4 A (max.)
- Inrush Current
- 20 A (max.)
- Internal Fuse Rating
- 10 A
- Output Voltage
- 12 VDC
- Output Current
- 6.25 A (max.)
- Output Power
- 75 W (max.)
- Output Hold-up Time
- 10 ms (min.)
- Output Startup Delay Time
- 100 ms (max.)
- Over-Voltage Protection
- 15.6 VDC (max.)
- Over-Current Protection
- 9 A (min.)
- Efficiency
- 87%
- Isolation
- 3k VDC (input to output) 3k VDC (system to field power)
Field Power Parameters
- Power Connector
- Screw-fastened Euroblock terminal
- No. of Power Inputs
- 1
- Input Voltage
- Nominal value: 24 VDC Acceptable range: 21.6 to 26.4 VDC
- Input Current
- 3 A (max.)
- Internal Fuse Rating
- 8 A
- Output Voltage
- 3 A (max.) [Input Voltage - 0.4] VDC (max., matching diode drop at 3 A)
- Over-voltage Protection
- 29 VDC (max.)
- Over-current Protection
- 5 A (min.)
Physical Characteristics
- Housing
- Plastic
- Dimensions
- 42 x 177 x 149.4 mm (1.65 x 6.97 x 5.88 in)
- Weight
- 713 g (1.57 lb)
- Installation
- DIN-rail mounting Rack mounting (with optional kit)
Standards and Certifications
- EMC
- EN 55032/35 EN 61000-6-2/-6-4
- EMI
- CISPR 32, FCC Part 15B Class A
- EMS
- IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m IEC 61000-4-4 EFT: Power: (DC) 1 kV; Signal: 1 kV IEC 61000-4-5 Surge: Power: (DC) 0.5 kV L-N, 1 kV L/N-PE; Signal: 1 kV; IO: 0.5 kV IEC 61000-4-6 CS: Power: (DC) 10 Vrms; Signal: 10 Vrms IEC 61000-4-8 PFMF: 30 A/m
- Safety
- UL 61010-1 UL 61010-2-201
- Shock
- IEC 60068-2-27 Half sine wave; acceleration: 15 g; time: 11 ms
- Vibration
- IEC 60068-2-6 DIN-rail mounted: 7 mm peak-peak (p-p) (2 to 8.42 Hz), 1 g (8.42 to 150 Hz) Rack mounted (with optional kit): 7 mm peak-peak (p-p) (2 to 8.42 Hz), 0.5 g (8.42 to 150 Hz)
- Package Vibration Test
- ISTA 1A
- Package Drop Test
- ISTA 1A
MTBF
- Time
- 954,606 hrs
- Standards
- Telcordia Standard SR-332
Environmental Limits
- Operating Temperature
- -40 to 75°C (-40 to 167°F) Note: Proper airflow is required in an environment with temperature > 65°C
- Storage Temperature (package included)
- -40 to 85°C (-40 to 185°F)
- Ambient Relative Humidity
- 5 to 95% (non-condensing)
- Altitude
- Up to 2000 m
Warranty
- Warranty Period
- 5 years
- Details