Specifications
Input/Output Interface
- Thermocouple Channels
- 8
- Isolation
- 3k VDC or 2k Vrms
Thermocouples
- Connector
- Spring-type Euroblock terminal
- Millivolt Accuracy
- ±0.1% FSR @ 25°C ±0.3% FSR @ -40 to 75°C
- Input Impedance
- 1 mega-ohms (min.)
- Millivolt Type
- ±19.532 mV ±39.062 mV Fault and over-voltage protection: -35 to +35 VDC (power off); -25 to +30 VDC (power on)
- Resolution
- 16 bits
- Sampling Rate
- All channels: 12 samples/sec Per channel: 1.5 samples/sec
- Sensor Type
- J, K, T, E, R, S, B, N
Power Parameters
- Power Consumption
- 24.1 mA @ 24 VDC
Physical Characteristics
- Dimensions
- 25 x 128.2 x 85.5 mm (0.98 x 5.05 x 3.37 in)
- Weight
- Under 80 g
- Wiring
- I/O cable, 14 to 28 AWG
Environmental Limits
- Operating Temperature
- -40 to 75°C (-40 to 167°F)
- Storage Temperature (package included)
- -40 to 85°C (-40 to 185°F)
- Ambient Relative Humidity
- 5 to 95% (non-condensing)
- Altitude
- 2000 m Note: Please contact Moxa if you require products guaranteed to function properly at higher altitudes.
Standards and Certifications
- EMC
- EN 55032/24, EN 61000-6-2/-6-4
- EMI
- CISPR 32, FCC Part 15B Class A
- EMS
- IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV IEC 61000-4-3 RS: 5100 MHz to 6000 MHz: 3 V/m IEC 61000-4-4 EFT: Power: 1 kV; Signal: 0.5 kV IEC 61000-4-5 Surge: Power: 2 kV; Signal: 1 kV IEC 61000-4-6 CS: 10 V IEC 61000-4-8 PFMF
- Railway
- EN 50121-4, EN 50155 (complies with a portion of EN 50155 specifications)
- Safety
- UL 508
- Shock
- IEC 60068-2-27
- Vibration
- IEC 60068-2-6
MTBF
- Time
- 2,324,891 hrs
- Standards
- Telcordia SR332
Warranty
- Warranty Period
- 5 years
- Details
- See www.moxa.com/warranty