Specifications
Input/Output Interface
- Digital Input Channels
- 16
- Isolation
- 3k VDC or 2k Vrms
Digital Inputs
- Connector
- Spring-type Euroblock terminal
- Voltage
- 24 to 110 VDC
- Debouncing Function
- Software enable/disable
- Debouncing Time
- 1 to 15 ms (software-selectable)
- I/O Mode
- DI
- Points per COM
- 8 channels
- Scan on Time
- 0.5 ms
- Scan Period
- 8 ms (typical)
- Sensor Type
- PNP
- Wet Contact (DI to COM)
- On: > 0.3 times external power voltage Off: < 0.15 times external power voltage
Digital Outputs
- Connector
- Spring-type Euroblock terminal
- I/O Mode
- DO or PWM
Power Parameters
- Power Consumption
- 12.6 mA @ 24 VDC
Physical Characteristics
- Dimensions
- 25 x 128.2 x 85.5 mm (0.98 x 5.05 x 3.37 in)
- Weight
- Under 80 g
- Wiring
- I/O cable, 16 to 28 AWG
Environmental Limits
- Operating Temperature
- -40 to 75°C (-40 to 167°F)
- Storage Temperature (package included)
- -40 to 85°C (-40 to 185°F)
- Ambient Relative Humidity
- 5 to 95% (non-condensing)
- Altitude
- 2000 m Please contact Moxa if you require products guaranteed to function properly at higher altitudes.
Standards and Certifications
- EMC
- EN 55032/24, EN 61000-6-2/-6-4
- EMI
- CISPR 32, FCC Part 15B Class A
- EMS
- IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV IEC 61000-4-3 RS: 5100 MHz to 6000 MHz: 3 V/m IEC 61000-4-4 EFT: Power: 1 kV; Signal: 0.5 kV IEC 61000-4-5 Surge: Power: 2 kV; Signal: 1 kV IEC 61000-4-6 CS: 10 V IEC 61000-4-8 PFMF
- Railway
- EN 50121-4, EN 50155
- Safety
- UL 508
- Shock
- IEC 60068-2-27
- Vibration
- IEC 60068-2-6
MTBF
- Time
- 1,115,244 hrs
- Standards
- Telcordia SR332
Warranty
- Warranty Period
- 5 years
- Details
- See www.moxa.com/warranty