MGate 5109-T
MGate 5109 Series1-port Modbus RTU/ASCII/TCP-to-DNP3 serial/TCP/UDP gateways
- Supports Modbus RTU/ASCII/TCP master/client and slave/server
- Supports DNP3 serial/TCP/UDP master and outstation (Level 2)
- DNP3 master mode supports up to 26600 points
- Supports time-synchronization through DNP3
- Effortless configuration via web-based wizard
- Built-in Ethernet cascading for easy wiring
- Embedded traffic monitoring/diagnostic information for easy troubleshooting and cloud data transmission for cost evaluation and analysis
- microSD card for configuration backup/duplication and event logs
- Status monitoring and fault protection for easy maintenance
- Redundant dual DC power inputs and relay output
- -40 to 75°C wide operating temperature models available
- Serial port with 2 kV isolation protection
Certifications ATEX · Iecex · UL Listed · CE
Ships from and sold by A5 IT, an authorized Moxa reseller.
Specifications
Ethernet Interface
- 10/100BaseT(X) Ports (RJ45 connector)
- 2 Auto MDI/MDI-X connection
- Magnetic Isolation Protection
- 1.5 kV (built-in)
Ethernet Software Features
- Industrial Protocols
- Modbus TCP Client (Master) Modbus TCP Server (Slave) DNP3 TCP Master DNP3 TCP Outstation
- Configuration Options
- Web Console (HTTP/HTTPS) Device Search Utility (DSU) Telnet Console
- Management
- ARP DHCP Client DNS HTTP HTTPS SMTP SNMP Trap SNMPv1/v2c/v3 TCP/IP Telnet SSH UDP NTP Client
- MIB
- RFC1213, RFC1317
- Time Management
- NTP Client
Security Functions
- Authentication
- Local database
- Encryption
- HTTPS AES-128 AES-256 SHA-256
- Security Protocols
- SNMPv3 SNMPv2c Trap HTTPS (TLS 1.3)
Serial Interface
- Console Port
- RS-232 (TxD, RxD, GND), 8-pin RJ45 (115200, n, 8, 1)
- No. of Ports
- 1
- Connector
- DB9 male
- Serial Standards
- RS-232/422/485
- Baudrate
- 50 bps to 921.6 kbps
- Data Bits
- 7, 8
- Parity
- None Even Odd Space Mark
- Stop Bits
- 1, 2
- Flow Control
- RTS Toggle (RS-232 only) RTS/CTS
- RS-485 Data Direction Control
- Automatic Data Direction Control (ADDC)
- Pull High/Low Resistor for RS-485
- 1 kilo-ohm, 150 kilo-ohms
- Terminator for RS-485
- 120 ohms
- Isolation
- 2 kV (built-in)
Serial Signals
- RS-232
- TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
- RS-422
- Tx+, Tx-, Rx+, Rx-, GND
- RS-485-2w
- Data+, Data-, GND
- RS-485-4w
- Tx+, Tx-, Rx+, Rx-, GND
Serial Software Features
- Configuration Options
- Serial Console
- Industrial Protocols
- Modbus RTU/ASCII Master Modbus RTU/ASCII Slave DNP3 Serial Master DNP3 Serial Outstation
Modbus RTU/ASCII
- Mode
- Master, Slave
- Functions Supported
- 1, 2, 3, 4, 5, 6, 15, 16, 23
- Max. No. of Commands
- 100
Modbus TCP
- Functions Supported
- 1, 2, 3, 4, 5, 6, 15, 16, 23
- Mode
- Client (Master), Server (Slave)
- Max. No. of Client Connections
- 16
- Max. No. of Server Connections
- 32
- Max. No. of Commands
- 100
DNP3 (Transparent)
- Max. No. of Master Connections
- 16
- Max. No. of Outstation Connections
- 32
DNP3 Serial
- Mode
- Master, Outstation
- Max. No. of Master Connections
- 1
- Max. No. of Outstation Connections
- 31
- Internal Master Database (MGate as DNP3 Master)
- Binary Inputs: 8192 points (256 points per outstation) Analog Inputs: 2048 points (64 points per outstation) Counters: 2048 points (64 points per outstation) Binary Outputs: 8192 points (256 points per outstation) Analog Outputs: 2048 points (64 points per outstation)
- Internal Outstation Database
- Binary Inputs: 8192 points Analog Inputs: 2048 points Counters: 2048 points Binary Outputs: 8192 points Analog Outputs: 2048 points Binary Input Events: 1024 Analog Input Events: 1024 Counter Events: 1024
DNP3 TCP/UDP
- Mode
- Master, Outstation
- Max. No. of Master Connections
- 1
- Max. No. of Outstation Connections
- 32
- Internal Master Database (MGate as DNP3 Master)
- Binary Inputs: 8192 points (256 points per outstation) Binary Outputs: 8192 points (256 points per outstation) Analog Inputs: 2048 points (64 points per outstation) Analog Outputs: 2048 points (64 points per outstation) Counters: 2048 points (64 points per outstation)
- Internal Outstation Database
- Binary Inputs: 8192 points Analog Inputs: 2048 points Counters: 2048 points Binary Outputs: 8192 points Analog Outputs: 2048 points Binary Input Events: 1024 Analog Input Events: 1024 Counter Events: 1024
Memory
- microSD Slot
- Up to 32 GB (SD 2.0 compatible)
Power Parameters
- Input Voltage
- 12 to 48 VDC
- Input Current
- 455 mA @ 12 VDC
- Power Connector
- Screw-fastened Euroblock terminal
Relays
- Contact Current Rating
- Resistive load: 2 A @ 30 VDC
Physical Characteristics
- Housing
- Metal
- IP Rating
- IP30
- Dimensions
- 36 x 105 x 140 mm (1.42 x 4.14 x 5.51 in)
- Weight
- 507 g (1.12 lb)
Environmental Limits
- Operating Temperature
- -40 to 75°C (-40 to 167°F)
- Storage Temperature (package included)
- -40 to 85°C (-40 to 185°F)
- Ambient Relative Humidity
- 5 to 95% (non-condensing)
Standards and Certifications
- EMC
- EN 55032/35
- EMI
- CISPR 32, FCC Part 15B Class B
- EMS
- IEC 61000-4-2 ESD: Contact: 8 kV; Air: 15 kV IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m IEC 61000-4-4 EFT: Power: 4 kV; Signal: 2 kV IEC 61000-4-5 Surge: Power: 2 kV; Signal: 2 kV IEC 61000-4-6 CS: 150 kHz to 80 MHz: 10 V/m; Signal: 10 V/m IEC 61000-4-8 PFMF
- Safety
- EN 62368-1 UL 508
- Hazardous Locations
- ATEX Class I Division 2 IECEx
- Freefall
- IEC 60068-2-32
- Shock
- IEC 60068-2-27
- Vibration
- IEC 60068-2-6 IEC 60068-2-64
MTBF
- Time
- 888,926 hrs
- Standards
- Telcordia Standard SR-332
Warranty
- Warranty Period
- 5 years
- Details
- See www.moxa.com/warranty