TCC-100I-T
TCC-100/100I SeriesIndustrial RS-232 to RS-422/485 converters with optional 2 kV isolation
- RS-232 to RS-422 conversion with RTS/CTS support
- RS-232 to 2-wire or 4-wire RS-485 conversion
- 2 kV isolation protection (TCC-100I)
- Wall mounting and DIN-rail mounting
- Plug-in terminal block for easy RS-422/485 wiring
- LED indicators for power, Tx, Rx
- Wide-temperature model available for -40 to 85°C environments
Certifications UL Listed · CE · FCC
Ships from and sold by A5 IT, an authorized Moxa reseller.
Specifications
Serial Interface
- No. of Ports
- 2
- Connector
- Terminal block
- Serial Standards
- RS-232 RS-422 RS-485
- Baudrate
- 50 bps to 921.6 kbps (supports non-standard baudrates)
- Pull High/Low Resistor for RS-485
- 1 kilo-ohm, 150 kilo-ohms
- RS-485 Data Direction Control
- ADDC (automatic data direction control)
- Terminator for RS-485
- N/A, 120 ohms, 120 kilo-ohms
- Isolation
- 2 kV (I models)
Serial Signals
- RS-232
- TxD, RxD, RTS, CTS, GND
- RS-422
- Tx+, Tx-, Rx+, Rx-, RTS (optional), CTS (optional), GND
- RS-485-2w
- Data+, Data-, GND
- RS-485-4w
- Tx+, Tx-, Rx+, Rx-, GND
Power Parameters
- Input Current
- 144 mA (max)
- Input Voltage
- 12 to 48 VDC
- No. of Power Inputs
- 1
- Overload Current Protection
- Supported
- Power Connector
- Terminal block (for DC models)
Physical Characteristics
- Housing
- Metal
- IP Rating
- IP30
- Dimensions
- 67 x 100.4 x 22 mm (2.64 x 3.93 x 0.87 in)
- Weight
- 148 g (0.33 lb)
- Installation
- Wall mounting DIN-rail mounting (with optional kit)
Environmental Limits
- Operating Temperature
- -40 to 85°C (-40 to 185°F)
- Storage Temperature (package included)
- -40 to 85°C (-40 to 185°F)
- Ambient Relative Humidity
- 5 to 95% (non-condensing)
Standards and Certifications
- EMC
- EN 55032/35
- EMI
- CISPR 32, FCC Part 15B Class A
- EMS
- IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV IEC 61000-4-3 RS: 80 MHz to 1 GHz: 3 V/m IEC 61000-4-4 EFT: Power: 1 kV; Signal: 0.5 kV IEC 61000-4-5 Surge: Power: 1 kV IEC 61000-4-6 CS: 150 kHz to 80 MHz: 3 V/m; Signal: 3 V/m IEC 61000-4-8 PFMF
- Safety
- UL 60950-1
- Vibration
- IEC 60068-2-6
- Environmental Testing
- IEC 60068-2-1 IEC 60068-2-3
MTBF
- Time
- 3,017,857 hrs
- Standards
- Telcordia (Bellcore), GB
Warranty
- Warranty Period
- 5 years
- Details
- See www.moxa.com/warranty
Documentation
| Name | Type | Version | Date |
|---|---|---|---|
| Datasheet for TCC-100/100I Series769.9 KB | Datasheet | v1.5 | Dec 04, 2024 |
| Declaration of Conformity for TCC-100I/100I-T296.3 KB | Declaration | v1.0 | May 08, 2024 |
| Declaration of Conformity for TCC-100/100I295.0 KB | Declaration | v1.0 | May 08, 2024 |
| QIG for TCC-100/100I Series2.1 MB | QIG | v12.2 | Jan 04, 2022 |
| 2D CAD for TCC-100 TOP483.0 KB | 2D CAD | — | Mar 27, 2015 |