PTC-101 Series
IEC 61850-3 Ethernet-to-fiber media converters

Features and Benefits
- 10/100BaseT(X) auto-negotiation and auto-MDI/MDI-X
- Link Fault Pass-Through (LFPT)
- Power failure alarm by relay output (LV model only)
- -40 to 85°C operating temperature range
- Redundant dual DC power inputs (LV model only)
- Integrated high-reliability power supply eliminates the need for external power transformer
Certifications
- Iec61850 3 Ieee1613 Black
- CE
- FCC
- UL REC
Introduction
The PTC-101 Ethernet-to-fiber media converters convert from 10/100BaseT(X) to 100BaseFX. Models are available with either SC, ST, or LC connectors. The PTC-101 converters eliminate the need for additional wiring, and support IEEE 802.3 and IEEE 802.3u/x protocols with 10/100M, full/half-duplex, and MDI/MDI-X auto-sensing to provide a total solution for your industrial Ethernet networks. The PTC-101 is compliant with mandatory sections of IEC 61850-3, covering operating temperature, power input voltage, surge, ESD, and vibration, as well as conformal coating and power insulation, making the media converters suitable for a variety of industrial applications.
Models in this series (12)












| — | PTC-101-M-SC-LV | PTC-101-M-ST-LV | PTC-101-M-LC-LV | PTC-101-S-SC-LV |
| Fiber Module Type | Multi-mode SC | Multi-mode ST | Multi-mode LC | Single-mode SC |
| Input Voltage | 20-72 VDC | 20-72 VDC | 20-72 VDC | 20-72 VDC |
| — | Add to Quote View Bag Buy from distributors (for USA only) | Add to Quote View Bag Buy from distributors (for USA only) | Add to Quote View Bag Buy from distributors (for USA only) | Add to Quote View Bag Buy from distributors (for USA only) |
| — | PTC-101-S-ST-LV | PTC-101-S-LC-LV | PTC-101-M-SC-HV | PTC-101-M-ST-HV |
| Fiber Module Type | Single-mode ST | Single-mode LC | Multi-mode SC | Multi-mode ST |
| Input Voltage | 20-72 VDC | 20-72 VDC | 85-264 VAC 88-300 VDC | 85-264 VAC 88-300 VDC |
| — | Add to Quote View Bag Buy from distributors (for USA only) | Add to Quote View Bag Buy from distributors (for USA only) | Add to Quote View Bag Buy from distributors (for USA only) | Add to Quote View Bag Buy from distributors (for USA only) |
| — | PTC-101-M-LC-HV | PTC-101-S-SC-HV | PTC-101-S-ST-HV | PTC-101-S-LC-HV |
| Fiber Module Type | Multi-mode LC | Single-mode SC | Single-mode ST | Single-mode LC |
| Input Voltage | 85-264 VAC 88-300 VDC | 85-264 VAC 88-300 VDC | 85-264 VAC 88-300 VDC | 85-264 VAC 88-300 VDC |
| — | Add to Quote View Bag Buy from distributors (for USA only) | Add to Quote View Bag Buy from distributors (for USA only) | Add to Quote View Bag Buy from distributors (for USA only) | Add to Quote View Bag Buy from distributors (for USA only) |
Specifications
Shown for PTC-101-M-LC-HV. Per-model differences are listed in the selection grid above.
Ethernet Interface
- 10/100BaseT(X) Ports (RJ45 connector)
- 1
- 100BaseFX Ports (multi-mode LC connector)
- 1
- Magnetic Isolation Protection
- 1.5 kV (built-in)
- Optical Fiber
- Read more 100BaseFX Multi-Mode Single-Mode Wavelength 1300 nm 1310 nm Max. TX -10 dBm 0 dBm Min. TX -20 dBm -5 dBm RX Sensitivity -32 dBm -34 dBm Link Budget 12 dB 29 dB Typical Distance 5 km a 4 km b 40 km c Saturation -6 dBm -3 dBm a. 50/125 µm, 800 MHz x km fiber optic cable b. 62.5/125 µm, 500 MHz x km fiber optic cable c. 9/125 µm single-mode fiber optic cable d. 9/125 µm single-mode fiber optic cable (80 km)
Power Parameters
- Input Voltage
- 100 to 240 VAC 100 to 240 VDC
- Input Current
- 350 to 200 mA @ 100 to 240 VAC 350 to 200 mA @ 100 to 240 VDC
- Overload Current Protection
- Supported
- Power Consumption
- 350 to 200 mA @ 100 to 240 VAC 350 to 200 mA @ 100 to 240 VDC
Physical Characteristics
- Housing
- Metal
- Dimensions
- 152.15 x 126.46 x 66.65 mm (5.99 x 4.86 x 2.62 in)
- Weight
- Product With Package: 952 g (2.09 lb) Product Only: 785 g (1.73 lb)
- Installation
- DIN-rail mounting
Environmental Limits
- Operating Temperature
- -40 to 85°C (-40 to 185°F)
- Storage Temperature (package included)
- -40 to 85°C (-40 to 185°F)
- Ambient Relative Humidity
- 5 to 95% (non-condensing)
Standards and Certifications
- EMC
- EN 55032/35
- EMI
- CISPR 32, FCC Part 15B Class A
- EMS
- IEC 61000-4-2 ESD: Contact: 8 kV; Air: 15 kV IEC 61000-4-3 RS: 80 MHz to 1 GHz: 3 V/m IEC 61000-4-4 EFT: Power: 4 kV; Signal: 4 kV IEC 61000-4-5 Surge: Power: 4 kV; Signal: 4 kV IEC 61000-4-6 CS: 150 kHz to 80 MHz: 10 V/m; Signal: 10 V/m IEC 61000-4-8 PFMF IEC 61000-4-11
- Environmental Testing
- IEC 60068-2-1 IEC 60068-2-14 IEC 60068-2-3
- Safety
- EN 62368-1 UL 62368-1 UL 60950-1
- Vibration
- IEC 60068-2-6
- Power Substation
- IEC 61850-3
MTBF
- Time
- 4,660,534 hrs
- Standards
- Telcordia SR332
Warranty
- Warranty Period
- 5 years
- Details
- See www.moxa.com/warranty
Resources
| Name | Type | Version | Date |
|---|---|---|---|
| Datasheet for PTC-101 Series799.5 KB | Datasheet | v1.7 | Aug 21, 2024 |
| Declaration of Conformity for PTC-101 Series314.4 KB | Declaration | v1.0 | Apr 29, 2024 |
| QIG for PTC-101 Series2.0 MB | QIG | v5.2 | May 06, 2021 |
| 2D CAD for PTC-101-M-LC-LV231.8 KB | 2D CAD | — | May 17, 2016 |
| 2D CAD for PTC-101-M-SC-LV TOP470.3 KB | 2D CAD | — | May 17, 2016 |
Need pricing on the PTC-101 Series?