MGate 5111 Series
1-port Modbus/PROFINET/EtherNet/IP to PROFIBUS slave gateways

Features and Benefits
- Converts Modbus, PROFINET, or EtherNet/IP to PROFIBUS
- Supports PROFIBUS DP V0 slave
- Supports Modbus RTU/ASCII/TCP master/client and slave/server
- Supports EtherNet/IP Adapter
- Supports PROFINET IO device
- Effortless configuration via web-based wizard
- Built-in Ethernet cascading for easy wiring
- Embedded traffic monitoring/diagnostic information for easy troubleshooting and cloud data transmission for cost evaluation and analysis
- Status monitoring and fault protection for easy maintenance
- microSD card for configuration backup/duplication and event logs
- Supports redundant dual DC power inputs and 1 relay output
- Serial port with 2 kV isolation protection
- -40 to 75°C wide operating temperature models available
Certifications
- ATEX
- Iecex
- UL Listed
- CE
Introduction
MGate 5111 industrial Ethernet gateways convert data from Modbus RTU/ASCII/TCP, EtherNet/IP, or PROFINET to PROFIBUS protocols. All models are protected by a rugged metal housing, are DIN-rail mountable, and offer built-in serial isolation. Modbus is one of the most widely used industrial communication protocols, and EtherNet/IP, PROFINET, and PROFIBUS are commonly used in factory automation and process automation. The MGate 5111 supports both Modbus RTU/ASCII/TCP master and slave modes, so that you can easily connect your Modbus device to PROFIBUS PLCs or DCSs, such as Siemens PLCs. For system integration, the MGate 5111 can connect to EtherNet/IP PLC/SCADA systems, such as Rockwell Automation PLCs, to PROFIBUS PLC/DCS systems, or between a new Siemens PLC system that supports PROFINET to an existing PROFIBUS system. The MGate 5111 gateways are designed for easy configuration and quick maintenance. A handy web console can be used to implement remote maintenance tasks, and the configuration wizard UI lets you quickly set up your gateway. A comprehensive collection of troubleshooting tools reduce configuration time and system downtime. The rugged design is suitable for industrial applications, such as factory automation, power, oil and gas, water and wastewater, and other process automation industries.
Models in this series (2)
| — | MGate 5111 | MGate 5111-T | — | — |
| Operating Temp. | 0 to 60°C | -40 to 75°C | ||
| — | Add to Quote View Bag Buy from distributors (for USA only) | Add to Quote View Bag Buy from distributors (for USA only) |
Specifications
Shown for MGate 5111. Per-model differences are listed in the selection grid above.
Ethernet Interface
- 10/100BaseT(X) Ports (RJ45 connector)
- 2 Auto MDI/MDI-X connection
- Magnetic Isolation Protection
- 1.5 kV (built-in)
Ethernet Software Features
- Industrial Protocols
- Modbus TCP Client (Master) Modbus TCP Server (Slave) PROFINET IO Device EtherNet/IP Adapter
- Configuration Options
- Web Console (HTTP/HTTPS) Device Search Utility (DSU) Telnet Console
- Management
- ARP DHCP Client DNS HTTP HTTPS SMTP SNMP Trap SNMPv1/v2c/v3 TCP/IP Telnet SSH UDP NTP Client
- MIB
- RFC1213, RFC1317
- Time Management
- NTP Client
Serial Interface
- Console Port
- RS-232 (TxD, RxD, GND), 8-pin RJ45 (115200, n, 8, 1)
- No. of Ports
- 1
- Connector
- DB9 male
- Serial Standards
- RS-232/422/485
- Baudrate
- 50 bps to 921.6 kbps
- Data Bits
- 7, 8
- Parity
- None Even Odd Space Mark
- Stop Bits
- 1, 2
- Flow Control
- RTS Toggle (RS-232 only) RTS/CTS
- RS-485 Data Direction Control
- Automatic Data Direction Control (ADDC)
- Pull High/Low Resistor for RS-485
- 1 kilo-ohm, 150 kilo-ohms
- Terminator for RS-485
- 120 ohms
- Isolation
- 2 kV (built-in)
Serial Signals
- RS-232
- TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
- RS-422
- Tx+, Tx-, Rx+, Rx-, GND
- RS-485-2w
- Data+, Data-, GND
- RS-485-4w
- Tx+, Tx-, Rx+, Rx-, GND
Serial Software Features
- Configuration Options
- Serial Console
- Industrial Protocols
- PROFIBUS DP-V0 Slave Modbus RTU/ASCII Master Modbus RTU/ASCII Slave
Modbus RTU/ASCII
- Mode
- Master, Slave
- Functions Supported
- 1, 2, 3, 4, 5, 6, 15, 16, 23
- Max. No. of Commands
- 128
- Input Data Size
- 2048 bytes
- Output Data Size
- 2048 bytes
Modbus TCP
- Mode
- Client (Master), Server (Slave)
- Functions Supported
- 1, 2, 3, 4, 5, 6, 15, 16, 23
- Max. No. of Client Connections
- 16
- Max. No. of Server Connections
- 32
- Max. No. of Commands
- 128
- Input Data Size
- 2048 bytes
- Output Data Size
- 2048 bytes
PROFIBUS Interface
- Industrial Protocols
- PROFIBUS DP
- No. of Ports
- 1
- Connector
- DB9 female
- Baudrate
- 9600 bps to 12 Mbps
- Isolation
- 2 kV (built-in)
- Signals
- PROFIBUS D+, PROFIBUS D-, RTS, Signal Common, 5V
PROFIBUS
- Rotary Switch
- PROFIBUS addresses 0-99 (addresses 100-125 supported through software configuration)
- Mode
- DP-V0 Slave
- Max. No. of Master Connections
- 1
- Max. No. of PROFIBUS I/O Modules
- 24
- Input Data Size
- 244 bytes
- Output Data Size
- 244 bytes
PROFINET
- Mode
- IO Device
- Max. No. of IO Controller Connections
- 1 (for read/write)
- Input Data Size
- 512
- Output Data Size
- 512
EtherNet/IP
- Mode
- Adapter
- CIP Objects Supported
- Identity Message Router Assembly Connection Manager TCP/IP interface Ethernet link Port
- Max. No. of Scanner Connections
- 1 (for read-only), 1 (for read/write)
- Input Data Size
- 496 bytes
- Output Data Size
- 496 bytes
Memory
- microSD Slot
- Up to 32 GB (SD 2.0 compatible)
Power Parameters
- Input Voltage
- 12 to 48 VDC
- Input Current
- 416 mA @ 12 VDC
- Power Connector
- Spring-type Euroblock terminal
Relays
- Contact Current Rating
- Resistive load: 2 A @ 30 VDC
Physical Characteristics
- Housing
- Metal
- IP Rating
- IP30
- Dimensions
- 45.8 x 105 x 134 mm (1.8 x 4.13 x 5.28 in)
- Weight
- 589 g (1.30 lb)
Environmental Limits
- Operating Temperature
- 0 to 60°C (32 to 140°F)
- Storage Temperature (package included)
- -40 to 85°C (-40 to 185°F)
- Ambient Relative Humidity
- 5 to 95% (non-condensing)
Standards and Certifications
- EMC
- EN 61000-6-2/-6-4
- EMI
- CISPR 32, FCC Part 15B Class A
- EMS
- IEC 61000-4-2 ESD: Contact: 8 kV; Air: 15 kV IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m IEC 61000-4-4 EFT: Power: 4 kV; Signal: 4 kV IEC 61000-4-5 Surge: Power: 2 kV; Signal: 2 kV IEC 61000-4-6 CS: 150 kHz to 80 MHz: 10 V/m; Signal: 10 V/m IEC 61000-4-8 PFMF
- Safety
- EN 62368-1 UL 61010-2-201
- Hazardous Locations
- ATEX Class I Division 2 IECEx
- Freefall
- IEC 60068-2-32
- Shock
- IEC 60068-2-27
- Vibration
- IEC 60068-2-6 IEC 60068-2-64
MTBF
- Time
- 718,131 hrs
- Standards
- Telcordia SR332
Warranty
- Warranty Period
- 5 years
- Details
- See www.moxa.com/warranty